Modular Heat Pump Inverter MCU-YHI series
Full-inverter power saving

Energy efficiency class 1 according to the dual classification scheme based on the seasonal energy efficiency ratio (SEER) during cooling and heating operation. Power saving up to 26% in the entire SEER range.

34 -150 kW Heating capacity;       33,5 - 130 kW Cooling capacity;



  Various applications

Various applications

This solution is suitable for conventional indoor use, as well as special process and sanitary conditions, cooling only operation, low temperatures and extreme heat, etc. The unit supports a full range of alternative applications.

Intelligent combination

Intelligent combination

Up to 16 fixed-speed modules (YH\YHE) and variable-speed inverter modules can be freely combined. This allows meeting various project demands, such as energy saving.

 All-round air intake

All-round air intake

The heat exchanger is made of two U-shaped parts, with 45% more area on the air side and uniform all-round air return.

Proprietary drive control program

Proprietary drive control program

The unit is driven by a BLDC motor, while the control program with 8,000 counts per second and double filtering prevents power outages at any frequency level.

Inverter driven operation and precise output adjustment

Inverter driven operation and precise output adjustment

The powerful inverter compressor supports stepless adjustment of capacity within 15% to 100%. It also performs well under partial load, avoiding frequent starts and stops. The use of EVI technology enables operation in extreme cold or heat.

 Balancing management

Balancing management

Partial  load takes priority during operation. When several units operate together, each compressor is frequency controlled through intelligent management, which ensures balanced operation in the energy-efficient area of the performance curve.

Technological design

Technological design
  • The heat pump components are completely concealed to prevent them from damaging
  • Improved heat exchange efficiency thanks to the increased air intake area
  • Sheet metal casing painted in ivory colour
  • Distinctive inverter design with the technology of enhanced vapour injection (EVI)
  • High-efficiency shell-and-tube heat exchanger
Communication and control features

Communication and control features
  • Modular design for easy combination of the units
  • Easy to use touch control panel (accessory)
  • Support of remote control via MODBUS

Partial load operation prioritized

When multiple modules are combined, the frequency of each compressor is intelligently controlled, with priority given to the operation in an energy-efficient partial load area. At the same time, compressor running time and load are balanced to facilitate uniform wear of each module compressor.

 

Patented 5-stage sound insulation for compressor room

Patented 5-stage sound insulation for compressor room
  1. Acoustic block. Green felt with butyl rubber material to frequency noises
  2. Ultra-silence acoustic panel absorber. High-density foaming damping material to effectively absorb vibration and noise across frequencies
  3. Hermetic soundproof box
  4. Suction and discharge copper pipe, oil separator, silencer, etc., placed in the compressor soundproof box
  5. Protection panel around the unit to further block noise
Industry's largest diameter axial fan under equal air flow

Industry's largest diameter axial fan under equal air flow

Sawtooth large impeller, low rotating speed, low fan speed, operating noise in low speed for dual blower as 30 dB.  The brushless full DC fan motor features stepless speed adjustment of 15-100% and more stable operation, achieving higher energy efficiency while reducing noises.

Frequency conversion and noise reduction

Frequency conversion and noise reduction

Three silent modes selectable
With wired controller settings, the unit automatically limits the operation frequency of the compressor and the fan and actively reduces noise to meet customers' higher requirements.

Operation range

Operation range

Thanks to many years of experience in the development and design of refrigeration equipment, the company has successfully implemented the technology enhaced vapour injection (EVI) and inverter technology and made a breakthrough in the operation of modular heat pumps, the operating range is increased.



Specifications

UnitsMCU035YHIMCU065YHIMCU130YHI
Rated cooling mode    
Cooling capacitykW33,565,0130
Power consumptionkW12,021,241,8
EERW/W2,793,063,11
Seasonal energy efficiency ratio (SEER)W/W4,604,554,55
Seasonal coeficient of perfomance (SCOP)W/W3,203,103,10
Rated heating mode    
Heating capacitykW34,075,0150
Power consumptionkW10,523,445,0

COP

Seasonal coeficient of perfomance (SCOP)

W/W

W/W

3,24

3,20

3,20

3,10

3,33

3,10

Power supply 380 V, 3 phases, 50 Hz380 V, 3 phases, 50 Hz380 V, 3 phases, 50 Hz
Water flow ratem3/h5,7611,222,4
Water perssure dropkPa304545
Type of water inlet/outlet pipe connection DN40 external threadDN 65 flange connectionDN65 flange connection
Operation mode Automatic microcontroller-based operationAutomatic microcontroller-based operationAutomatic microcontroller-based operation
Compressor type Inverter scroll compressor with enhanced vapour injection (EVI)Inverter scroll compressor with enhanced vapour injection (EVI)Inverter scroll compressor with enhanced vapour injection (EVI)
Number of compressorspcs.112
Fan type Low-noise inverter axial fanLow-noise inverter axial fanLow-noise inverter axial fan
Number of fanspcs.122
Air flow ratem3/h130002600047000
Refrigerant type R410AR410AR410A
Dimensions, LxWxHmm1170×846×16942000×950×20202250x1150x2260
Net weightkg285600960
Operating weightkg3006601060
Noise leveldB(A)50 – 6150 – 6750 – 67
Maximum total electric powerkW2031,563
Maximum operating currentA30,550100


Notes:
1. Rated cooling capacity and rated power consumption during cooling have been tested at the rated water flow rate, outlet water temperature 7 °C and ambient temperature 35 °C (dry bulb).
2.Rated heating capacity has been tested at the rated water flow rate, outlet water temperature 45 °C and ambient air temperature 7 °C (dry bulb) / 6 °C (wet bulb).